DC voltage drop

DC voltage drop: use dc current, one-way cable length, conductor cross-sectional area. Review the formula, worked example and calculation steps.

Inputs

Use the units shown

Check material properties, site conditions and applicable standards before using this estimate for design, procurement or safety decisions.

RESULT
—

Enter your values and select Calculate.

Formula & explanation
Drop V = current × resistivity × (2×one-way length)/area

Variables & units

DC current
A · minimum 0, maximum 1000000000000
One-way cable length
m · minimum 0, maximum 1000000000000
Conductor cross-sectional area
mm² · minimum 0.000001, maximum 1000000000000
Conductor resistivity at operating temperature
Ω·mm²/m · minimum 0.000001, maximum 1000000000000
Supply voltage
V · minimum 0.000001, maximum 1000000000000

Worked example

10 A, 20 m one-way, 2.5 mm² and 0.0175 Ω·mm²/m gives 2.8 V drop.

Assumptions

Two-conductor DC circuit at constant current; supply voltage is used only for the percentage. Not AC impedance, three-phase design or cable ampacity.

Formula version 1.0.0. JavaScript floating-point arithmetic applies. Results display up to 6 decimal places; stored values retain available precision. Use the units shown.